MEGABOARD Testing & Technical

Testing

ReGen Building Solutions takes its responsibilities for supplying products extremely seriously. To ensure we supply products that are Fit for Purpose, we have and continue to invest in testing to ensure the products we supply direct or third party products we supply as part of our systems meet our quality requirements.

ReGen Building Solutions has worked with manufacturers, suppliers, NATA testing labs, universities and associations to develop a range of tests for the products we supply to our end-user customer. All recommended 3rd party products have been tested by the suppliers to ensure the products perform and interact appropriately with MEGABOARD to ensure long term durability.

Our 3rd party suppliers include:

3M – Glues, sealants and tapes

Valspar – Granosite render, internal/external paints and sealants

Astec – Renders and paint

SteedForm – Lamination

Our Testing partners include:

Ian Berry and Associates NATA approved – Waterproofing and wind loads

Laminex – Bend strength NATA approved

Ignis Fire Solutions – BAL Rating/non-combustibility

University of South Australia – Bend tests

AWTA – Thermal Resistance NATA approved

SLR – Acoustics

Bureau Veritas – Asbestos NATA approved

Independent Certification

FMG Engineering

Acronem Consulting

MEGABOARD Dimensional and Weight Properties

MEGABOARD comes in a range of different sizes, thicknesses and edging finishes.

Thickness
mm
Length
mm
Width
mm
M2 Weight
kg
EDGING
Recessed Square
6 2400 1200 2.88 17
6 2700 1200 3.24 19
6 3000 1200 3.6 21
8 2400 1200 2.88 28
8 2700 1200 3.24 31
8 3000 1200 3.6 35
10 2400 1200 2.88 34
10 2700 1200 3.24 38
10 3000 1200 3.6 42
12 2400 1200 2.88 36
12 2700 1200 3.24 41
12 3000 1200 3.6 45

 

MEGABOARD Testing

MEGABOARD goes through independent testing incorporating 16 separate tests before boards are accepted for cladding internal or external applications. The tests for the boards are outlined in the below table and must pass prior to being accepted by ReGen Building Solutions.

Tests are based on the following testing regimes and must pass before being accepted

Testing Requirements for acceptance

8 mm MEGABOARD

Test No Inspection Item Units Requirement Test Results Pass/Fail
1 Density t/m3 1.2<p≤1.5 1.21 Pass
2 Rupture Strength MPa ≥ 15 29.62 Pass
3 Impact Strength kj/m2 ≥ 2.5 6.92 Pass
4 Water Ratio % ≤ 8 2.71 Pass
5 Dry Shrinkage % ≤ 3 0.17 Pass
6 Bulking Factor % ≤ 6 0.23 Pass
7 Screw Holding n/mm ≥ 20 110 Pass
8 Water Absorbtion % ≤ 20 12.71 Pass
9 Softening coefficient ≥0.75 0.8 Pass
10 Embrittlement cooefficient ≥ 0.7 0.9 Pass
11 Side wet bend curvature ≤ 3 1.14 Pass
12 Dry Bend ≤ 3 2.7 Pass
13 Chloride Ion Ratio % ≤ 3 1.95 Pass
14 Halogenation No moisture No Halogenation No moisture No Halogenation Pass
15 Hydrophobicity Hydrophilic
16 Hydrophilicty ≥ 20 55 Pass

10 mm MEGABOARD

次Test No Inspection Item Units Requirement Test Results Pass/Fail
1 Density t/m3 1.2<p≤1.5 1.18 Pass
2 Rupture Strength MPa ≥ 10 25.37 Pass
3 Impact Strength kj/m2 ≥ 2.0 6.51 Pass
4 Water Ratio % ≤ 8 2.86 Pass
5 Dry Shrinkage % ≤ 3 0.18 Pass
6 Bulking Factor % ≤ 6 0.25 Pass
7 Screw Holding n/mm ≥ 20 120.2 Pass
8 Water Absorbtion % ≤ 20 13.52 Pass
9 Softening coefficient ≥0.75 0.77 Pass
10 Embrittlement cooefficient ≥ 0.7 1.4 Pass
11 Side wet bend curvature ≤ 3 0.73 Pass
12 Dry Bend ≤ 3 2.9 Pass
13 Chloride Ion Ratio % ≤ 3 2.49 Pass
14 Halogenation No moisture No Halogenation No moisture No Halogenation Pass
15 Hydrophobicity Hydrophilic
16 Hydrophilicty ≥ 20 25 Pass
17 Falling ball impact ≥ 5 6 Pass

12 mm MEGABOARD

Test No Inspection Item Units Requirement Test Results Pass/Fail
1 Density t/m3 1.0<p≤1.2 1.08 Pass
2 Rupture Strength MPa ≥ 8 22.49 Pass
3 Impact Strength kj/m2 ≥ 2.0 5.74 Pass
4 Water Ratio % ≤ 8 2.53 Pass
5 Dry Shrinkage % ≤ 3 0.15 Pass
6 Bulking Factor % ≤ 6 0.19 Pass
7 Screw Holding n/mm ≥ 15 105.24 Pass
8 Water Absorbtion % ≤ 25 13.95 Pass
9 Softening coefficient ≥0.75 0.82 Pass
10 Embrittlement cooefficient ≥ 0.7 1.08 Pass
11 Side wet bend curvature ≤ 3 1.14 Pass
12 Dry Bend ≤ 3 1.59 Pass
13 Chloride Ion Ratio % ≤ 3 2.2 Pass
14 Halogenation No moisture No Halogenation No moisture No Halogenation Pass
15 Hydrophobicity Hydrophilic
16 Hydrophilicty ≥ 20 110 Pass
17 Falling ball impact ≥ 5 5 Pass

Cladding span tables

MEGABOARD span tables 6mm

Wind Classification Within 1200mm of Building Corners Elsewhere Externally
As per AS4055-2012 Max support spacing e.g batten(mm) Max Fastener Spacing (mm) Max support spacing e.g batten(mm) Max Fastener Spacing (mm)
N1 450 200 450 300
N2 450 200 450 300
N3 200 450 300
N4 200 300
N5 200 300
N6 200 300

 

MEGABOARD span tables 8mm

Wind Classification Within 1200mm of Building Corners Elsewhere Externally
As per AS4055-2012 Max support spacing e.g batten(mm) Max Fastener Spacing (mm) Max support spacing e.g batten(mm) Max Fastener Spacing (mm)
N1 600 200 600 300
N2 600 200 600 300
N3 450 200 600 300
N4 450 200 450 300
N5 450 200 450 300
N6 200 450 300

MEGABOARD span tables 10mm

Wind Classification Within 1200mm of Building Corners Elsewhere Externally
As per AS4055-2012 Max support spacing e.g batten(mm) Max Fastener Spacing (mm) Max support spacing e.g batten(mm) Max Fastener Spacing (mm)
N1 600 200 600 300
N2 600 200 600 300
N3 450 200 600 300
N4 450 200 450 300
N5 450 200 450 300
N6 200 450 300

MEGABOARD span tables 12mm

Wind Classification Within 1200mm of Building Corners Elsewhere Externally
As per AS4055-2012 Max support spacing e.g batten(mm) Max Fastener Spacing (mm) Max support spacing e.g batten(mm) Max Fastener Spacing (mm)
N1 600 200 600 300
N2 600 200 600 300
N3 600 200 600 300
N4 600 200 600 300
N5 600 200 600 300
N6 600 200 600 250

Terms and Conditions

Asbestos Report

External Cladding

Soffits and Eaves

Sacrificial formwork

Coating specifications External Wattle/Solver/Granosite

Coating specifications Internal Wattle/Solver/Granosite

Coating Specification Exterior Rockcote

 

 